SERIES
www.king-electric.com
King Electrical Manufacturing Company / 9131 10th Avenue South, Seattle, WA 98108 / phone 206.762.0400 / fax 206.763.7738
in-built line voltage
CAPILLARY TUBE STYLE
Control Range:
40°F to 90°F (4°C - 32°C)
Power Source: 125 VAC
240 VAC
277 VAC
Switch Action: Single Pole,
Single Throw, make on
temperature rise
Differential: 2°F
Ratings: Non-inductive
25 Amps @ 120VAC
25 Amps @ 240 VAC
SPECIFICATIONS
SNAP ACTION SWITCHING: Instant, positive response. No arcing. No
burning of contacts, to shorten switch life. No TV snow, no radio static.
Enclosed for protection against dirt and corrosion.
LIQUID-FILLED SENSING ELEMENT: This extra sensitive remote
capillary bulb dependably and accurately registers the slightest temperature
change instantly.
VENTED FRAME: Top and bottom to maintain normal temperature in
outlet box.
AIR PASSAGE: No obstruction of air across bi-metal sensor.
FACTORY SEALED and CALIBRATED: Engineered for accurate,
dependable performance. Field adjustment not required.
ENCLOSED TERMINALS: To prevent contact with grounded faces.
RATING: 25 Amps continuous at 120, 208, 240 Volts AC. Non-inductive.
22 Amps continuous at 277 Volts AC. Non-inductive.
MAXIMUM RANGE: 40° to 117°F (4°C - 47°C)
AVERAGE DIFFERENTIAL: Approximately 5°F at 50% of rated load.
CYCLE RATE: Approximately 2 - 4 per hour at 50% of rated load.
DESIGN FEATURE SPECIFICATIONS
Mounting: 6-32 threaded holes
on 1 5/16" (33mm) centers
Shaft: Type 1 (clockwise to raise
temperature setting)
Sensor: Liquid-filled capillary
and bulb
Capillary length: 3 wire: 4 1/16"
2 wire: 3½"
Bulb diameter: 3 wire: 5/16"
2 wire: ¼"
Weight: .3 lbs/.14kg (single pole)
Lead Wires: 125°C 14AWG
UL File: E16835
TWO WIRE
single pole
maximum temperature 105° F
THREE WIRE
single pole
maximum temperature 107° F
ELECTRICAL RATING CHART
VOLTS
WATTS
208
240
277
5200
6000
6925
120
3000
AMPS
25
25
22
25
Part # 275-2822-00
C1-25
SERIES
KB
KCC
KC
KCF
KFUH
Part # 275-5011-00
C1-25
SERIES
LPW
KBP
1 5/16"
1 5/16"
Vue de la page 0